Strany 1 - CONDENSING UNIT

SERVICE MANUALASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AHCONDENSING UNIT

Strany 2

2. Dimensions H Model (mm) A B C DE F HASE-18AH 760 530 290 315270 285 590ASE-24AH 842 560 335 360312 324 695ASE-36AH 990 624 366 39634

Strany 3 - Model Names of Outdoor Units

3. Service Space >30cm>60cm>30cm >200cm(Wall or obstacle)Air inletAir outletAir inletMaintain channel>60cmObstacleFix with boltDeep f

Strany 4 - Features

1 1, For 18,24,36K units, All the outdoor fan have a outdoor fan with fixed speed. Normally the outdoor fan runs with the compressor. The outdoor fan

Strany 5 - Outdoor Units

2 When in heating mode, For the units with two outdoor fan motors, in some occasions, one motor will stop: When in cooling mode, When in heating mod

Strany 6

ASE-18AH 4. Wiring Diagrams

Strany 7

ASE-24AH

Strany 8

A S E - 3 6 A HS.V.XT 3XT 4213S. V.XT 7XT6NHEAT ERCOMPCN100-208XT3T5RT4K1RT3XP8-9H-PROT201XT5-7XT4KM1HEATCN201XT5CN100CN2 00KM1T20 1COMPXS8-9FAN3CAP3F

Strany 9 - Model Ratedcurrent

ASE-48AH ASE-60AH 1, 2, 3 are just input signal to outdoor PCBIf 1 and N are 220V, the compressor will start.If 2 and N are 2

Strany 10 - 2. Dimensions

5. Electric CharacteristicsHz Voltage Min. Max.ASE-18AH 50 220-240V 198V 254VASE-24AH 50 220-240V 198V 254VASE-36AH 50 380-415V 342V 418VASE-48AH 50 3

Strany 11 - Service Space

6. Operation Limits Operation mode Outdoor temperature(℃) Room temperature(℃) Cooling & Heating Cooling operation 18~43 17~30 Heating operatio

Strany 13

7. Sound Levels 18000Btu/h-48000Btu/h 60000Btu/h MicrophoneOutdoor UnitH1.0m Note: H= 0.5 × height of outdoor unit

Strany 14 - 4. Wiring Diagrams

LEDs’ for the indication of outdoor trouble Type Contents LED1 LED2 LED3 Trouble Phase sequence Flash Off Off Trouble Lack of phase(A,B) Fl

Strany 15 - ASE-24AH

Lack of phase Check the power supply, is it 3 phase, 380-415V? Check the connection between power supply and terminal, is the voltage in outdoor termi

Strany 16 - A S E - 3 6 A H

d. Protection of pressure or temp. e. Open-circuit and short-circuit trouble of T3 Is connection to connector of temp. sensor good? Check the

Strany 17

f. Open-circuit and short-circuit trouble of T4 g. High temperature protection of condenser Is connection to connector of temp. sensor good? Chec

Strany 18 - 5. Electric Characteristics

9. Q&A (1) What is the value of evaporation temperature which is used for calculate cooling capacity? The evaporation temperature for all of i

Strany 19 - 6. Operation Limits

Installation 1.Precaution on Installation ... 132 2.Vacuum Dry and Leakage Checking...

Strany 20 - Microphone

1. Precaution on Installation 1). Measure the necessary length of the connecting pipe, and make it by the following way. a. Connect the indoor unit a

Strany 21 - 8. Troubleshooting

2. Vacuum Dry and Leakage Checking 2.1 Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out o

Strany 22

②. Special vacuum dry procedure l This vacuum dry method is used in the following conditions: l There’s moisture when flushing the refrigerant pipe

Strany 23

Outdoor Units - appearance 18,000Btu/h 24,000Btu/h 30,000~36,000Btu/h 48,000Btu/h-60,000Btu/h Model Names of Outdoor UnitsUniversal Outdoo

Strany 24

3. Additional Refrigerant Charge Caution ● Refrigerant cannot be charged until field wiring has been completed. ● Refrigerant may only be charged aft

Strany 25 - 9. Q&A

4. Water Drainage 4.1 Gradient and Supporting 4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short

Strany 26 - Installation

For Four-way cassette 4.4 Convergent drainage 4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe over

Strany 27 - Heating)

Stop the air conditioner running, turn off the power, and put back the cover.③ l Stop the air conditioner. After 3 minutes, check if it has abnormi

Strany 28

5. Insulation Work 5.1 Insulation material and thickness 5.1.1. Insulation material Insulation material should adopt the material which is able to e

Strany 29

For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the

Strany 30

7. Test Operation (1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points

Strany 31 - 4. Water Drainage

PARTS GUIDEASE-18AH, ASE-24AH, ASE-36AH, ASE-48AH, ASE-60AH CONDENSING UNIT

Strany 32 - For Four-way cassette

Exploded viewmodel: ASE-18AH

Strany 33

Spare part listNo Description Part Code NoteQty Price Code 1 Top cover assembly 201237400324 12 Supporter assembly of fan motor 201237890017 13 Cond

Strany 34 - 5. Insulation Work

Features High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins. Anti

Strany 35 - 6. Wiring

Exploded viewmodel:ASE-24AH

Strany 36 - 7. Test Operation

Spare part listNo Description Part Code NoteQty Price Code 1Top cover assembly201248100266 12Fan motor fixing foam202245500001 13Supporter assembly

Strany 37

Exploded viewmodel:ASE-36AH

Strany 38 - Exploded view

Spare part listNo Description Part Code NoteQty Price Code 1 Top cover assembly 201248700174 12 Rear supporter 2012487G0011 13 Supporter assembly of

Strany 39 - Spare part list

Exploded viewmodel:ASE-48AH, ASE-60AH (=ASF-60A outdoor unit)

Strany 40

Spare part listNo Description Part Code NoteQty Price Code 1Top cover assembly 201275600087 12Axial flow fan 201100300102 23Rear-left supporting boa

Strany 41 - MODEL: ASE-24AH

No Description Part Code NoteQty Price Code 1 Top cover assembly 201275600087 12 Axial flow fan 201100300102 23 Rear-left supporting board 2012756001

Strany 42

Outdoor Units 1. Specifications ... 100 2. Dimensions ...

Strany 43

Model ASE-18AH ASE-24AH Code 220037802190 220075301210 Power supply V-ph-Hz 220~240-1-50 220~240-1-50 Max. input consumption W 2950

Strany 44

Model ASE-36AH Code 220075500682 Power supply V-ph-Hz 380~415-3-50 Max. input consumption W 4950 Max. input current A 10

Strany 45 - MODEL: ASE-48AH

Model ASE-48AH ASE-60AH Code 220075701250 220075800650 Power supply V-ph-Hz 380~415-3-50 380~415-3-50 Max. input consumption W 6300 7500 Max

Strany 46

Model RatedcurrentASE-18AH 15AASE-24AH 18AASE-36AH 10A 3 phasesASE-48AH 12.5A 3 phasesASE-60AH 12.6A 3 phases